5)Structural data and main characteristics:
No. Model Cores×Nominal Section mm² Number of Cores/ Diameter mm Outside Diameter of Cable mm DC Resistance at 20℃ Ω/km Insulated Resistance at 70℃ MΩ.km
Copper Core Tinned Copper Core

2601

AVVR

2×0.08

7/0.12

4.1 2.7×4.1

247

254

0.018

2602

2×0.12

7/0.15

4.3 2.9×4.3

158

163

0.016

2603

2×0.2

12/0.15

4.7 3.1×4.6

92.3

95

0.014

2604

2×0.3

16/0.15

5.3 3.4×5.2

69.2

71.2

0.014

2605

2×0.4

23/0.15

5.7 3.5×5.6

48.2

49.6

0.013

2606

3×0.12

7/0.15

4.5

158

163

0.016

2607

3×0.2

12/0.15

4.9

92.3

95

0.014

2608

3×0.3

16/0.15

5.7

69.2

71.2

0.014

2609

3×0.4

23/0.15

6

48.2

49.6

0.013

2610

4×0.12

7/0.15

4.9

158

163

0.016

2611

4×0.2

12/0.15

5.4

92.3

95

0.014

2612

4×0.3

16/0.15

6.2

69.2

71.2

0.014

2613

4×0.4

23/0.15

6.6

48.2

49.6

0.013

2614

5×0.12

7/0.15

5.3

158

163

0.016

2615

5×0.2

12/0.15

5.8

92.3

95

0.014

2616

5×0.3

16/0.15

6.7

69.2

71.2

0.014

2617

5×0.4

23/0.15

7.2

48.2

49.6

0.013

2618

6-7×0.12

7/0.15

5.7

158

163

0.016

2619

6-7×0.2

12/0.15

6.3

92.3

95

0.014

2620

6-7×0.3

16/0.15

7.3

69.2

71.2

0.014

2621

6-7×0.4

23/0.15

7.8

48.2

49.6

0.013

2622

10×0.12

7/0.15

7.2

158

163

0.016

2623

10×0.2

12/0.15

8

92.6

95

0.014

2624

10×0.3

16/0.15

9.7

69.2

71.2

0.014

2625

10×0.4

23/0.15

10.4

48.2

49.6

0.013

2626

12×0.12

7/0.15

7.4

158

163

0.016

No. Model Cores×Nominal Section mm² Number of Cores/ Diameter mm Outside Diameter of Cable mm DC Resistance at 20℃ Ω/km Insulated Resistance at 70℃ MΩ.km
Copper Core Tinned Copper Core

2627

AVVR

12×0.2

12/0.15

8.2

92.3

95

0.014

2628

12×0.3

16/0.15

10.1

69.2

71.2

0.014

2629

12×0.4

23/0.15

10.8

48.2

49.6

0.013

2630

14×0.12

7/0.15

7.8

158

163

0.016

2631

14×0.2

12/0.15

9.1

92.3

95

0.014

2632

14×0.3

16/0.15

10.6

69.2

71.2

0.014

2633

14×0.4

23/0.15

11.3

48.2

49.6

0.013

2634

16×0.12

7/0.15

8.2

158

163

0.016

2635

16×0.2

12/0.15

9.6

92.3

95

0.014

2636

16×0.3

16/0.15

11.1

69.2

71.2

0.014

2637

16×0.4

23/0.15

11.9

48.2

49.6

0.013

2638

19×0.12

7/0.15

9.1

158

163

0.016

2639

19×0.2

12/0.15

10.1

92.3

95

0.014

2640

19×0.3

16/0.15

11.7

69.3

71.2

0.014

2641

19×0.4

23/0.15

12.6

48.2

49.6

0.013

2642

24×0.12

7/0.15

10.6

158

163

0.016

2643

24×0.2

12/0.15

11.7

92.3

95

0.014

2644

24×0.3

16/0.15

14.2

69.2

71.2

0.014

2645

24×0.4

23/0.15

15.2

48.2

49.6

0.013

Remark: Fire-retardant wires and cables are added with ZR- before their model numbers, for example ZR-AVVR.
  • Previous Product: PVC Insulated Shielded Cable at Rated Voltage of 450/750V or less

  • Next Product: PVC Insulated Flexible Cable for Connecting at Rated Voltage of 450/750V or less
  • Return
  • Hits:1105  Add Time:2007-7-13 【Print】 【Close
    Home | About Us | Products | Guest Book | Contact Us
    Copyright © 2007 sh-lixin.com All Rights Reserved.
    Address:Shanghai NanChen Road 297 (Shanghai University of New South Gate)